Review the available liquid cooling solutions for energy storage applications.
CTHB-S3HW300350FU44-380-1
1. Dual-System Design
2.Horizontal Structure for Easy Integration
3. High Cooling & Heat Exchange Capacity
4. Cooling, Heating & Circulation Modes
5. Precise Temperature Control
6. Wide Ambient Temperature Range
7. Smart Communication Interface
Cooltechx BESS liquid cooling temperature control module for ESS thermal management, featuring ≥30kW cooling, 25kW heating, ±1°C control and CAN/RS485.
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Cooling Capacity | kW | ≥30kW (L45°C/W23°C) |
| 2 | Heat Exchange Capacity | kW | ≥35kW (L45°C/W55) |
| 3 | Energy Efficiency Ratio (EER) | W/W | ≥2.0@(L45°C/W23°C) |
| 4 | Heating Capacity | kW | 25 |
| 5 | Rated Flow Rate | L/min | 300 |
| 6 | Rated Flow Rate | L/min | 80 |
| 7 | Lift / Head | m | 15@300L/min |
| 8 | Lift / Head | m | 20@80L/min |
| 9 | Operating Ambient Temperature | °C | -30~55 |
| 10 | Storage Ambient Temperature | °C | -40~70 |
| 11 | Noise Level | dBA | ≤80dBA@1m |
| 12 | Altitude | m | ≤4000 |
| 13 | Refrigerant | – | R410A |
| 14 | Applicable Cooling Medium | – | 50% Ethylene Glycol Pure Aqueous Solution |
| 15 | Liquid Temperature Control Accuracy | °C | ±1 |
| 16 | Water Pressure Display Accuracy | bar | 0.1 |
| 17 | Coolant Set Temperature Range | °C | 10~35 |
| 18 | Dimensions | mm | 2000×650×1500 |
| 19 | Net Weight | kg | ≤600 |
| 20 | Color | – | RAL 9003 |
| 21 | Electrical Control Protection Class | – | IP55 |
| 22 | Corrosion Protection Class | – | C3 |
| 23 | Inlet/Outlet Pipe Connection Type | – | Φ50.8 Card Disc |
| 24 | Maximum Water Circuit Pressure Capacity | kPa | 800 |
| 25 | Power System / Power Supply Standard | – | 3/PE AC 400V 50Hz |
| 26 | Rated Power | kW | ≤15 (L50°C/W25°C) |
| 27 | Maximum Input Power | kW | ≤29 |
| 28 | No-load Loss | W | ≤100 |
| 29 | Maximum Starting Current | A | ≤65 |
| 30 | Communication Requirement | – | CAN/RS485 |
| 31 | Software Version | – | – |
| 32 | ROHS Compliance | – | Compliant with ROHS |
| 33 | Design Life | Year | ≥10 |
| 34 | Water Makeup Volume | L | 8 |
| 35 | Expansion Tank Volume | L | 32L |
| 36 | Pressure Relief Valve Pressure | Bar | 3 |
Compare the available liquid cooling systems, review rated cooling conditions, and prepare the project information needed for a faster technical quotation.
Review the available liquid cooling solutions for energy storage applications.
Understand how cooling capacity, flow rate and test conditions affect selection.
Organize heat load, ambient conditions, liquid circuit and installation requirements before requesting a quote.
At Cooltechx, every cooling solution is backed by dedicated manufacturing facilities, standardized production processes, and rigorous quality control. From assembly to performance testing, we focus on delivering reliable thermal management solutions for demanding industrial applications.
Cooltechx is a brand integrating R&D, manufacturing, sales, and service. Our staff comes from Fortune 500 companies with more than 20 years of experience in the air-conditioning industry.
Our R&D technical teams can support customization, which means that if you have different requirements, higher standards, or more functional needs, we will give you the most cost-effective cooling solution.
Cooltechx cabinet air conditioner sample is available, ordering any amount of product is welcomed. The sample is of good quality at a reasonable price.
Advanced temperature control technology ensures even temperature distribution, which is critical for performance and longevity.
Emphasizes energy efficiency and energy-saving potential, using phase-change storage materials and virtual energy storage technology to increase efficiency and reduce energy consumption.
The technology is mature, and the product is reliable and stable. Liquid cooling and air cooling technologies have varying levels of maturity and application ranges in the market.
Initial investment cost and maintenance costs are key considerations for customers. Although liquid cooling systems have higher initial costs, they may offer lower overall costs in the long term.
Noise control and space requirements are key design considerations. Air cooling systems are quieter but may occupy more space, while liquid cooling systems are more compact.
Equipped with an intelligent control system capable of real-time monitoring and temperature adjustments, automatically optimizing operating modes to improve energy efficiency.
Effectively addresses overheating issues with adequate safety measures in place to ensure safe system operation.
Get In Touch With Cooltechx